Honeywell MC-TAIH03 (51309136-175) High-Level Analog Input Field Termination

Honeywell MC-TAIH03 (51309136-175) High-Level Analog Input Field Termination Assembly

Honeywell MC-TAIH03


🔧 Product Overview

The Honeywell MC-TAIH03 (Part Number: 51309136-175) is a High-Level Analog Input Field Termination Assembly (FTA) designed for integration with Honeywell’s Experion PKS and TPS control systems. This module facilitates the connection of field devices, such as transmitters and sensors, to the control system, ensuring accurate data acquisition and reliable system performance.


📊 Technical Specifications

Feature Specification
Model MC-TAIH03 (51309136-175)
Input Channels 16
Input Type High-Level Analog (Voltage)
Input Range 0–10 V DC / 4–20 mA
Input Impedance High (typically 10 MΩ)
Accuracy ±0.1% of Full Scale
Common Mode Rejection ≥70 dB
Normal Mode Rejection ≥19 dB
Isolation 1500 VDC Optical Isolation
Mounting DIN Rail or Panel Mount
Dimensions 152 mm × 120 mm × 20 mm
Weight Approximately 0.5 kg
Compliance CE Marked, Conformal Coating

⚙️ Installation Instructions

  1. Preparation: Ensure the system is powered down before installation to prevent electrical hazards.
  2. Mounting: Attach the MC-TAIH03 module to a DIN rail or panel, ensuring secure fixation and proper alignment.
  3. Wiring:
    • Connect the field device outputs to the input terminals of the module.
    • For voltage inputs, ensure correct polarity and voltage levels.
    • For current inputs, connect the positive lead to the input terminal and the negative lead to the common terminal.
  4. Termination: Use appropriate termination resistors if required, especially for current loop inputs, to ensure signal integrity.
  5. Power-Up: After wiring, power up the system and verify the module’s operation through the control system interface.

🛠️ Maintenance Guidelines

  • Regular Inspection: Periodically check for loose connections, signs of wear, or corrosion on terminals.
  • Cleaning: Use a dry, anti-static cloth to clean the module’s exterior. Avoid using liquids or solvents.
  • Calibration: Perform calibration checks as per the manufacturer’s recommendations to maintain measurement accuracy.
  • Firmware Updates: Keep the module’s firmware updated to ensure compatibility with the latest system features and improvements.
  • Documentation: Maintain records of all maintenance activities, including calibration and firmware updates, for future reference.

⚠️ Safety Precautions

  • Electrical Safety: Always disconnect power before performing installation or maintenance to prevent electric shock.
  • ESD Protection: Use anti-static wrist straps and mats when handling the module to prevent damage from electrostatic discharge.
  • Proper Grounding: Ensure that all equipment is properly grounded to avoid electrical hazards.
  • Environmental Conditions: Install the module in environments that meet the specified temperature and humidity ranges to ensure optimal performance.
  • Qualified Personnel: Only qualified personnel should perform installation and maintenance to ensure safety and compliance with standards.

🔗 Similar Products

For similar products and alternatives, consider the following options:

Model Description Link
MC-TAIH13 Redundant High-Level Analog Input FTA (16 Inputs) Link
MC-TSTX03 Smart Transmitter Interface FTA (16 Inputs) Link
MC-TAIH22 Enhanced Power High-Level Analog Input FTA (16 Inputs) Link
MC-TSTX13 Redundant Smart Transmitter Interface FTA (16 Inputs) Link
MC-TAIH52 High-Level Analog Input FTA (16 Inputs) Link

For more information and to explore additional products, visit the official Honeywell product page: Honeywell Product Page.

Share this story: