ABB | 3BSC690087R1 | AO895 S800 Intrinsically Safe HART Analog Output Module

Product Description

The ABB AO895, part number 3BSC690087R1, is an 8-channel analog output module for the ABB S800 I/O system. It provides 4–20 mA current outputs with integrated HART communication and intrinsic safety interface components.

The module is designed to connect control-system output signals to compatible field instruments in hazardous-area applications. Typical devices include control valves, positioners, and electro-pneumatic current-to-pressure converters.

Each channel can deliver up to 20 mA into a field load, with current limiting at approximately 22 mA under overload conditions. All eight channels form one isolation group, electrically isolated from the ModuleBus and power supply.

The AO895 receives its output-stage power from the 24 VDC supply connections and is designed for use with ABB TU890 or TU891 Module Termination Units. The correct termination unit and hazardous-area installation arrangement must be selected according to the application and applicable certification requirements.

Product Parameters

  • Brand: ABB
  • Model: AO895
  • Order Number: 3BSC690087R1
  • Product Series: S800 I/O
  • Product Name: Intrinsically Safe HART Analog Output Module
  • Product Type: Analog Output Module
  • Number of Channels: 8
  • Output Signal: 4–20 mA
  • Signal Type: Unipolar, single-ended
  • HART Communication: Supported on all 8 channels
  • Resolution: 12 bit
  • Maximum Normal Output Current: 20 mA per channel
  • Overload Current Limit: Approximately 22 mA
  • Maximum Output Load: 750 Ω under specified operating conditions
  • Isolation: Eight channels isolated as one group from ground, ModuleBus, and power supply
  • Rated Insulation Voltage: 50 V
  • Intrinsic Safety: Integrated interface components
  • Output Protection: Short-circuit-proof, current-limited outputs
  • Compatible Module Termination Units: TU890, TU891
  • Supply Arrangement: 24 VDC supplied through the termination unit connections
  • Mounting System: ABB S800 I/O
  • Width: 45 mm
  • Height: 119 mm
  • Depth: 102 mm; approximately 111 mm including connector
  • Weight: Approximately 0.21 kg
  • Place of Manufacture: Not independently verified
  • Product Status: Confirm the condition of the supplied unit
  • Country of Origin: Confirm from the product label

Main Features

  • Eight independent 4–20 mA analog output channels.
  • HART communication support on every output channel.
  • Integrated intrinsic safety interface components.
  • Designed for compatible hazardous-area field instrument connections.
  • 12-bit output resolution.
  • Group isolation across all eight channels.
  • Short-circuit-proof and current-limited output design.
  • Supports Ex-certified I/P converters and compatible control actuators.
  • Compatible with ABB TU890 and TU891 termination units.
  • Designed for integration into ABB S800 I/O and distributed control systems.

Typical Applications

  • ABB System 800xA distributed control systems
  • ABB Freelance automation systems
  • Hazardous-area process instrumentation
  • Control valve and positioner control
  • Electro-pneumatic I/P converter applications
  • Oil and gas processing facilities
  • Chemical and petrochemical plants
  • Refinery automation
  • Industrial flow, pressure, and temperature control loops
  • Remote analog control of compatible field devices

Installation and Commissioning

  1. Confirm the complete catalog number 3BSC690087R1 and AO895 model designation.
  2. Verify that the host S800 I/O system supports the AO895 module.
  3. Select the correct termination unit, TU890 or TU891, according to the installation and hazardous-area requirements.
  4. Isolate the relevant 24 VDC supply before installing or removing the module.
  5. Inspect the module, termination unit, connectors, and mounting position for damage or contamination.
  6. Install the termination unit according to ABB S800 I/O installation instructions.
  7. Insert the AO895 into the correct module position and ensure that it is securely seated.
  8. Connect the field devices to the corresponding channel terminals using the approved wiring diagram.
  9. Verify field-device polarity, loop wiring, cable shielding, and grounding arrangements.
  10. Confirm that the field-device load is within the specified output load limits.
  11. Configure the eight output channels in the ABB control-system engineering environment.
  12. Set the required output scaling, engineering units, and HART communication parameters.
  13. Apply the 24 VDC supply and inspect the module status indicators.
  14. Test each output channel using a calibrated current measurement instrument.
  15. Verify HART communication with compatible field instruments.
  16. Confirm that hazardous-area wiring and intrinsic safety installation requirements are satisfied before placing the system into service.

Daily Maintenance and Care

  • Check the module RUN, FAULT, WARNING, and HART communication indicators.
  • Monitor analog output values against the controller’s requested setpoints.
  • Inspect terminal connections and field wiring for loose contacts or corrosion.
  • Check the 24 VDC supply and termination unit connections.
  • Monitor HART communication interruptions and device diagnostic messages.
  • Inspect field instruments for abnormal loop resistance or wiring faults.
  • Verify output current using calibrated test equipment during scheduled maintenance.
  • Keep the cabinet clean and maintain appropriate operating temperatures.
  • Record channel faults, communication errors, and maintenance activities.
  • Follow the site’s hazardous-area inspection and maintenance schedule.

Troubleshooting and Common Questions

Q1: What is the ABB AO895 3BSC690087R1?

It is an eight-channel analog output module for ABB S800 I/O systems, featuring 4–20 mA outputs, HART communication, and integrated intrinsic safety interface components.

Q2: Does every channel support HART?

Yes. The AO895 provides HART communication on all eight output channels.

Q3: Which termination units are compatible?

ABB specifies TU890 and TU891 Module Termination Units for the AO895. Select the appropriate unit according to the installation and hazardous-area requirements.

Q4: What is the maximum output current?

Each channel can drive up to 20 mA under normal operating conditions. The output is limited to approximately 22 mA during overload conditions.

Q5: Can the AO895 drive control valves?

Yes. It can provide 4–20 mA control signals to compatible field devices, including control valve positioners and electro-pneumatic converters, provided their electrical requirements are within the module specifications.

Q6: Why is the measured output current lower than the requested value?

Possible causes include incorrect channel wiring, excessive loop resistance, an incorrect 24 VDC supply, field-device wiring problems, or an output-channel fault. Check the configured output value and measure the loop current at the appropriate test point.

Q7: What should be checked if HART communication fails?

Check field-device compatibility, loop wiring, polarity, communication configuration, signal integrity, and the applicable HART device settings. Also inspect the module and controller diagnostics.

Q8: Is AO895 interchangeable with AO890?

No, not as a direct functional replacement. Both modules provide intrinsically safe analog outputs, but AO895 supports HART communication while AO890 does not. Confirm system configuration and engineering requirements before considering a substitution.

Q9: Does AO895 support redundant operation?

No. ABB’s product data identifies AO895 as a non-redundant analog output module. Do not assume that it provides redundant output operation.

Safety Precautions

  • Isolate the relevant power supply before installing or removing the module.
  • Follow ABB S800 I/O installation instructions.
  • Use the correct TU890 or TU891 termination unit.
  • Observe the intrinsic safety parameters and hazardous-area certification requirements.
  • Do not exceed the specified output current or load resistance.
  • Verify field wiring and polarity before energizing the system.
  • Do not modify intrinsic safety circuits or approved wiring arrangements.
  • Use suitable test equipment and approved procedures in hazardous locations.
  • Installation and maintenance must be performed by qualified personnel.

Recommended ABB S800 I/O Models

The following are related ABB analog I/O modules and termination units. Their signal types and functions differ, so they are not all direct replacements for AO895.

  1. AO890 – 8-channel intrinsically safe analog output module without HART
  2. AO845A – 8-channel redundant or single analog output module with HART
  3. AO815 – 8-channel HART analog output module
  4. AO810V2 – 8-channel analog output module
  5. AO820 – 4-channel universal analog output module
  6. AI895 – 8-channel intrinsically safe HART analog input module
  7. AI890 – 8-channel intrinsically safe analog input module
  8. AI893 – 8-channel temperature input module
  9. AI845 – Analog input module for S800 I/O
  10. AI830 – 8-channel analog input module
  11. TU890 – S800 Module Termination Unit for intrinsically safe applications
  12. TU891 – S800 Module Termination Unit
  13. TU810 – Compact S800 Module Termination Unit
  14. TU812 – S800 Module Termination Unit
  15. TU814 – S800 Module Termination Unit
Share this story: