ABB Bailey | IMMFP01 | INFI 90 Multi-Function Processor Module

Product Description

The ABB Bailey IMMFP01 is a Multi-Function Processor (MFP) module designed for the INFI 90 and Network 90 distributed control systems. It serves as a central processing unit for industrial process automation, executing control strategies, processing system data, and coordinating communication with other controller and I/O modules.

The IMMFP01 uses a 32-bit microprocessor operating at 16 MHz and supports multiple programming methods, including function codes, C, BASIC, BATCH, ladder logic, and user-defined functions.

The module supports analog, sequential, and logic control applications. It also provides serial communication interfaces for connecting compatible stations and external devices.

The IMMFP01 is suitable for power generation, chemical processing, petrochemical facilities, and other industrial installations requiring reliable operation of legacy Bailey INFI 90 control systems.

ABB BAILEY CONTROLS infi 90 IMMFP01 MULTI-FUNCTION PROCESSOR MODULE  Image 1 of 4

Main Features

  • 32-bit microprocessor operating at 16 MHz
  • Designed for ABB Bailey INFI 90 / Network 90 systems
  • Multi-function process control capabilities
  • Supports analog, sequential, and logic control
  • Multiple programming languages and control methods
  • Two RS-232-C ports or one RS-232-C and one RS-485 port, depending on configuration
  • Supports redundant 1 Mbaud communication links
  • 512 KB ROM, 256 KB RAM, and 64 KB NVRAM
  • Single-slot installation in a standard INFI 90 module mounting unit

Product Parameters

  • Brand: ABB Bailey Controls
  • Model: IMMFP01
  • Product Name: Multi-Function Processor Module
  • Product Series: INFI 90 / Network 90
  • Product Type: DCS CPU / Processor Module
  • Microprocessor: 32-bit, 16 MHz
  • External Bus: 16-bit
  • ROM: 512 KB
  • RAM: 256 KB total
  • NVRAM: 64 KB total
  • Available RAM: 163,248 bytes
  • Available NVRAM: 62,656 bytes
  • Serial Interfaces: Two RS-232-C, or one RS-232-C and one RS-485, depending on configuration
  • Maximum Serial Link Rate: 19.2 kbaud
  • Redundant Communication Link: 1 Mbaud
  • Station Support: Up to 64 IISAC01 stations at 40 kbaud or 8 NDCS03 / NDIS01 stations at 5 kbaud
  • Power Requirements: +5 V DC at 2 A
  • Typical Power Consumption: 10 W
  • Mounting: One slot in a standard INFI 90 module mounting unit
  • Dimensions: 35.56 × 177.80 × 298.45 mm
  • Operating Temperature: 0 to 70°C
  • Relative Humidity: 5–95% up to 55°C, non-condensing; 5–45% above 55°C
  • Place of Manufacture: Not independently confirmed
  • Country of Origin: Verify from product label
  • Product Status: Verify actual stock condition
  • Discontinued Status: Legacy product; confirm current lifecycle status

Installation and Commissioning

  1. Confirm that the existing controller uses an INFI 90 or compatible Network 90 module mounting unit.
  2. Verify the IMMFP01 model and hardware revision against the original equipment documentation.
  3. Back up the controller application, configuration, and relevant process-control data before replacement.
  4. Isolate the module mounting unit power supply according to site procedures.
  5. Record the original module position and switch settings.
  6. Inspect the replacement module, edge connectors, and mounting slot for damage or contamination.
  7. Install the processor in the designated slot.
  8. Verify module address and communication settings using the appropriate DIP-switch configuration.
  9. Check the serial communication arrangement and termination hardware.
  10. Restore power and inspect the module status indicators.
  11. Verify communication with associated control stations and I/O modules.
  12. Confirm that the control application executes correctly before returning the process to normal operation.

Daily Maintenance and Care

  • Monitor processor status indicators and controller diagnostics.
  • Check communication links for errors or unexpected interruptions.
  • Inspect module connectors and mounting-unit contacts during scheduled maintenance.
  • Maintain proper cabinet temperature and ventilation.
  • Keep the control cabinet clean and free from moisture and conductive dust.
  • Maintain current backups of application programs and configuration settings.
  • Check power-supply stability and module operating conditions.
  • Record module replacement, configuration changes, and maintenance activities.

Troubleshooting and Common Questions

Q1: What is the main function of the IMMFP01?

A: It executes process-control strategies and coordinates data exchange between the INFI 90 controller and associated I/O and communication modules.

Q2: Which control systems support the IMMFP01?

A: It is designed for ABB Bailey INFI 90 and Network 90 control-system installations. Confirm the specific controller and mounting-unit configuration before replacement.

Q3: What programming languages does it support?

A: The documented programming methods include C, BASIC, BATCH, ladder logic, function codes, and user-defined functions.

Q4: What communication interfaces are available?

A: Depending on the configuration, the module provides two RS-232-C ports or one RS-232-C and one RS-485 port.

Q5: What should be checked if the processor fails to start?

A: Check the +5 V DC supply, module seating, DIP-switch settings, processor diagnostics, memory configuration, and communication connections.

Q6: Can the IMMFP01 be replaced by an IMMFP02?

A: Do not assume direct interchangeability. The IMMFP02 has its own hardware and configuration requirements. Verify the controller architecture, software, and replacement instructions.

Q7: Does the IMMFP01 support redundant communication?

A: Yes. Its documented specifications include a 1 Mbaud redundant serial communication link.

Safety Precautions

  • Isolate power before inserting or removing the module.
  • Follow ABB Bailey ESD handling procedures.
  • Verify module addressing and switch settings before commissioning.
  • Back up control programs and configuration data before replacement.
  • Do not change communication wiring without checking the system drawings.
  • Confirm the required termination hardware for serial connections.
  • Perform testing and commissioning through qualified DCS personnel.

Recommended ABB Bailey Related Models

The following modules belong to the ABB Bailey INFI 90 / Network 90 automation family. They serve different functions and are not all direct replacements for IMMFP01.

  1. IMMFP02 – Multi-Function Processor Module.
  2. IMMFP03 – Multi-Function Processor Module.
  3. IMMFP03B – Multi-Function Processor with expanded memory.
  4. IMMFP11 – Harmony Rack Multi-Function Processor.
  5. IMMFP12 – Harmony Rack Multi-Function Processor.
  6. IMMFC04 – Multi-Function Controller.
  7. IMMFC05 – Multi-Function Controller.
  8. IMMPI01 – Multi-Function Processor Interface Module.
  9. IMCOM03 – Controller Communication Module.
  10. IMCOM04 – Controller Communication Module.
  11. IMDSI13 – Digital Input Slave Module.
  12. IMDSI22 – Digital Input Module.
  13. IMDSO01 – Digital Slave Output Module.
  14. IMDSO02 – Digital Output Module.
  15. IMFAI01 – Isolated Analog Input Module.
Share this story: