ABB | CC-U/STD | Universal Analog Signal Converter

Product Description

The ABB CC-U/STD Universal Analog Signal Converter, part number 1SVR040000R1700, is designed to convert and condition standard analog signals for industrial measurement and control systems. It supports a wide range of selectable voltage, current, and resistance input signals, making it suitable for interfacing field instruments with PLC, DCS, and other automation equipment.

The converter provides three-way electrical isolation between the input, output, and power supply circuits. This helps reduce ground-loop effects and protects connected equipment from electrical interference. Its input and output ranges are configured using side-mounted DIP switches, while front-panel controls allow gain and offset adjustment.

The unit also features short-circuit-protected signal outputs, plug-in connection terminals, and configurable low-fail-safe or high-fail-safe behavior when an input signal is interrupted. A green LED indicates that the supply voltage is present.

Product Parameters

  • Brand: ABB
  • Model: CC-U/STD
  • Order Number: 1SVR040000R1700
  • Product Name: Universal Analog Signal Converter
  • Product Series: CC-U
  • Product Type: Analog Signal Converter / Signal Conditioner
  • Rated Supply Voltage: 24–48 V DC / 24 V AC, 50/60 Hz
  • Input Signal Range: ±0.9 mA to ±55 mA; ±45 mV to ±11 V; resistance input from 470 Ω to 1 MΩ
  • Output Signal Range: 0 to ±55 mA; 0 to ±11 V
  • Electrical Isolation: Three-way isolation between input, output, and supply
  • Configuration: Side-mounted DIP switches
  • Adjustment: Front-panel gain and offset controls
  • Output Protection: Short-circuit protected
  • Connection: Plug-in terminals
  • Mounting: DIN rail
  • Dimensions: 22.5 × 105 × 120 mm (W × H × D)
  • Net Weight: Approx. 0.125 kg
  • Country of Origin: Verify from the product nameplate and packaging
  • Product Status: Legacy product; verify current availability
  • Replacement Information: Check ABB’s current signal-conditioning range before selecting a substitute

Technical Specifications and Features

  1. Universal Signal Conversion
    Supports multiple standard and non-standard analog input and output ranges. This flexibility allows different field signal types to be adapted to the requirements of connected control equipment.
  2. Three-Way Electrical Isolation
    Separates the input, output, and power supply circuits to help prevent unwanted electrical interaction and ground-loop problems.
  3. Flexible DIP-Switch Configuration
    Side-mounted DIP switches provide selectable input and output ranges. Correct switch settings are essential for accurate signal conversion.
  4. Gain and Offset Adjustment
    Front-panel controls allow adjustment of signal gain and offset to compensate for differences between field instruments and control-system scaling.
  5. Configurable Input Failure Response
    The output response to an interrupted input voltage signal can be configured for low-fail-safe or high-fail-safe operation. The selected behavior should match the control-system design.
  6. Short-Circuit-Protected Outputs
    Output protection helps reduce the risk of damage during wiring faults or accidental output short circuits.
  7. Plug-In Connection Terminals
    Removable terminals simplify wiring, inspection, and replacement during maintenance.

Industrial Applications

  • PLC and DCS analog signal interfacing
  • Process measurement and control loops
  • Voltage-to-current and current-to-voltage signal conversion
  • Industrial temperature, pressure, and flow measurement systems
  • Instrumentation signal conditioning
  • Electrical control cabinets and automation panels
  • Signal isolation between field instruments and control equipment
  • Industrial machinery and process equipment

Installation and Commissioning

  1. Confirm the model and supply rating. Verify that the installed unit is CC-U/STD, part number 1SVR040000R1700.
  2. Disconnect power before installation or wiring.
  3. Mount the converter on a compatible DIN rail and ensure adequate cabinet clearance.
  4. Check the input signal type and range from the field instrument documentation.
  5. Set the input and output ranges using the DIP-switch configuration chart for this exact model.
  6. Connect the input, output, and supply terminals according to the ABB wiring diagram.
  7. Check polarity and terminal assignments before energizing the unit.
  8. Apply the specified supply voltage and confirm that the green supply LED illuminates.
  9. Apply a known input signal and measure the output with a calibrated instrument.
  10. Adjust gain and offset where necessary, then verify the complete signal range.
  11. Test the configured input-failure response before returning the control loop to service.

Daily Maintenance and Care

  • Check the green supply LED during routine cabinet inspections.
  • Inspect plug-in terminals for loose connections, discoloration, or corrosion.
  • Keep the converter free from dust, moisture, and excessive heat.
  • Check that the DIP-switch settings remain consistent with the control-system documentation.
  • Compare input and output readings during scheduled calibration.
  • Inspect signal cables and shielding for damage or poor termination.
  • Record gain and offset settings before making adjustments.
  • Replace units showing intermittent output, unstable readings, or physical damage.

Troubleshooting and Common Questions

Q1: The green LED does not illuminate. What should be checked?

Check the supply voltage, terminal wiring, polarity where applicable, and the condition of the power source. Confirm that the supply matches the 24–48 V DC or 24 V AC rating.

Q2: Why is the output signal incorrect?

Check the selected input and output ranges, DIP-switch positions, input wiring, and gain and offset settings. Also verify that the field instrument is producing the expected signal.

Q3: Can this converter handle both voltage and current signals?

Yes. The CC-U/STD supports configurable voltage and current input and output ranges, as well as resistance input ranges within its specified limits.

Q4: What is the purpose of three-way isolation?

It electrically separates the input, output, and supply circuits to help reduce ground-loop interference and unwanted electrical coupling.

Q5: What happens if the input signal is interrupted?

The converter can be configured to respond using a low-fail-safe or high-fail-safe output behavior. The selected setting must agree with the application’s control philosophy.

Q6: Can the CC-U/STD be replaced by another signal converter?

A replacement must match the required input and output ranges, supply voltage, isolation requirements, response characteristics, mounting arrangement, and failure behavior. Confirm compatibility before substitution.

Q7: Is the CC-U/STD suitable for direct connection to every PLC analog input?

No. The converter’s output range must match the electrical and scaling requirements of the receiving PLC or DCS input channel.

Safety Precautions

  • Disconnect power before wiring, removing, or replacing the converter.
  • Do not exceed the specified input, output, or supply limits.
  • Follow the ABB DIP-switch configuration and wiring instructions.
  • Confirm signal polarity and terminal assignments before energizing.
  • Do not change fail-safe settings without reviewing the control-system requirements.
  • Verify the complete signal loop before placing the equipment into operation.

Recommended Related ABB Models

The following models belong to ABB’s signal-conversion and control-product range. They are related product options, not all direct replacements for CC-U/STD.

  1. CC-U/STD – Universal analog signal converter, 24–48 V DC / 24 V AC version.
  2. CC-U/STD – Universal analog signal converter, 110–240 V AC supply version, order code 1SVR040001R0400.
  3. CC-U/STDR – Universal signal converter with two threshold relay outputs.
  4. 1SVR040010R0000 – CC-U/STDR version with 24–48 V DC / 24 V AC supply.
  5. 1SVR040011R2500 – CC-U/STDR version with high-voltage AC/DC supply.
  6. CC-E I/I – Current-to-current signal converter.
  7. CC-E U/I – Voltage-to-current signal converter.
  8. CC-E I/U – Current-to-voltage signal converter.
  9. CC-E U/U – Voltage-to-voltage signal converter.
  10. CM-IWN – ABB current monitoring relay family.
  11. CM-MPS – ABB three-phase monitoring relay family.
  12. CM-PVS – ABB voltage monitoring relay family.
  13. CM-ESS – ABB single-phase monitoring relay family.
  14. MACX MCR-UI-UI-NC – Analog signal conditioner from Phoenix Contact, an alternative to evaluate rather than an ABB model.
  15. 1SVR040000R1700 – ABB CC-U/STD, the same model and order number for identification and spare-parts matching.
Share this story: