ABB | DSAI130D | 3BSE003127R1 | Analog Input Board

The ABB DSAI130D (Part Number 3BSE003127R1) is a high-density analog input module designed for the Advant Controller 400 series and S800 I/O systems. This board serves as the critical interface between field sensors—such as temperature transmitters, pressure transducers, and flow meters—and the central processing unit. It is engineered to provide precise signal conversion and robust electrical isolation, ensuring that sensitive control logic remains protected from field-side interference while maintaining high data integrity for process automation.

Product Specifications

For more information and availability, please visit the product page: DSAI130D

  • Manufacturer: ABB

  • Model Number: DSAI130D

  • Part Number: 3BSE003127R1

  • Input Channels: 16 Differential Channels

  • Input Range: 0 to 20 mA, 4 to 20 mA, 0 to 10 V, 0 to 5 V (Software configurable)

  • Resolution: 12-bit plus sign

  • Accuracy: 0.1% of full scale (Typical)

  • Input Impedance: 250 ohms (Current) / >1 Mohm (Voltage)

  • Isolation: Groupwise isolated from the system backplane

  • Dimensions: 180 mm x 25 mm x 120 mm

  • Weight: 0.35 kg (0.77 lbs)

  • Country of Origin: Sweden

Application Fields

  • Petrochemical Refining: Monitoring of pressure and temperature loops in hazardous areas.

  • Water Treatment: Integration of flow rate and pH sensors for automated dosage control.

  • Metal Processing: Feedback loops for furnace temperature and hydraulic pressure systems.

  • Power Generation: Analog data acquisition for turbine auxiliary systems and boiler control.

  • Paper and Pulp: Precision measurement for tension control and moisture sensing in paper machines.

Product Instructions

Installation of the DSAI130D should only be performed while the system rack is powered down, unless the specific I/O station is explicitly rated for “Hot Swap” operation. The module should be inserted into the I/O slot until the connectors are fully seated and the locking tabs click into place. Field wiring should be connected to the corresponding terminal base (e.g., TU810 or TU812). It is highly recommended to use shielded twisted-pair cabling for all analog signals to minimize electromagnetic noise. The shield should be grounded at a single point, typically at the I/O cabinet end. Configuration of the input types (Current vs. Voltage) is handled via the ABB engineering software (such as Control Builder M), and the module will indicate its status via the “Run” and “Fault” LEDs on the front panel.

Q&A: Common Questions

How do I switch a channel from 4-20mA current to 0-10V voltage? The conversion is primarily software-defined in the hardware configuration of your controller. However, for current inputs, the DSAI130D utilizes an internal shunt resistor. Ensure that the terminal base wiring matches the hardware configuration to prevent overcurrent or signal clipping.

What does a flashing red ‘Fault’ LED signify? A flashing fault LED often indicates a configuration mismatch or an external channel error, such as a wire break (if configured for 4-20mA). A steady red LED usually points to an internal hardware failure or a self-test error during startup.

Does the DSAI130D support HART protocol? The standard DSAI130D is a basic analog input board. For HART communication (to pass through smart transmitter data), a specialized HART-compatible module from the S800 series, such as the DSAI130DA or similar, is usually required.

Can I mix voltage and current inputs on the same board? Yes, channels are generally configurable in groups; however, it is best practice to verify the specific grouping limitations in the S800 I/O User Manual to ensure the electrical isolation requirements for your specific sensors are met.

Related Model Recommendations

  • ABB DSAI130 3BSE000311R1

  • ABB DSAI133 3BSE000325R1

  • ABB DSAO120A 3BSE006110R1

  • ABB DSDI110 3BSE000331R1

  • ABB DSDO115 3BSE000341R1

Share this story: