The ABB REF545 (Model REF545EM133AAAB, Part 1MRS110040-001) is a multifunctional Feeder Protection Controller from the ABB Relion® 500 series. Designed for protection, control, measurement, and supervision of utility and industrial distribution feeders, this unit is a sophisticated numerical relay capable of handling complex protection schemes in medium-voltage power systems. Its modular architecture supports advanced communication protocols and programmable logic. For technical datasheets, software tools, and procurement, please visit the ABB Relion Product Portal.

📊 Technical Specifications
-
Series: Relion 500 Series
-
Model: REF545EM133AAAB
-
Part Number: 1MRS110040-001
-
Function: Feeder protection, control, and measurement
-
Communication: Ethernet, LON, SPA, IEC 60870-5-103 (configurable)
-
Design: Digital/Numerical microprocessor-based
-
Mounting: Panel-mounted, draw-out design
-
Manufacturer: ABB
🏗️ Application Areas
-
Medium-voltage distribution networks
-
Substation automation systems
-
Industrial primary and secondary distribution feeders
-
Complex feeder schemes requiring integrated control and protection
⚙️ Product Operation & Installation
Manual/Automatic Mode Switching The REF545 is a numerical relay configured via software (e.g., CAP 505 or PCM600). Manual control modes (Remote/Local) are typically handled via the front panel user interface or hardwired inputs that switch the logic between manual operation and automatic SCADA control.
Emergency Stop Operation The relay does not have a physical “E-Stop” button. However, it integrates into the site safety system as a high-speed protection device. When a fault (e.g., overcurrent, earth fault) is detected, the relay logic processes the trip command to the circuit breaker’s shunt trip coil instantaneously.
Mechanical Installation Requirements
-
Fixing Method: Flush-mount into the switchgear panel cutout. Use the provided mounting kit to ensure the front-panel seal remains IP54-compliant.
-
Space Distance: Ensure a minimum of 100 mm clearance at the rear for cable terminations and at least 50 mm around the sides for airflow.
-
Thermal Dissipation: Being a digital device with a large LCD screen, ensure the panel is ventilated. Operating temperatures exceeding +55°C may degrade the life of the display backlight and internal electrolytic capacitors.
Electrical Wiring
-
Terminal Definitions: All connections are made to the rear terminal blocks. The unit uses standardized wiring diagrams provided in the technical manual specific to the “AAAB” configuration.
-
Wire Gauge: Use 2.5 mm² multi-strand copper wire for CT/VT inputs to ensure low-impedance paths. Use shielded, twisted-pair cables for all communication (RS-485/Ethernet) to maintain signal integrity.
-
Grounding: A dedicated PE (Protective Earth) terminal is provided on the chassis. Use a flexible copper braid to bond this directly to the substation grounding grid to prevent high-frequency noise from corrupting the internal microprocessor.
💡 Frequently Asked Questions (Q&A)
Q: What do I need to configure this relay? A: You will need the ABB PCM600 software suite or the legacy CAP 505 configuration tool, along with the specific connectivity package (ConnPack) corresponding to the REF545 firmware version.
Q: How do I perform a firmware update? A: Firmware updates should only be performed by trained personnel. It requires a stable serial/Ethernet connection to the unit and the latest firmware image file directly from ABB’s support portal. Caution: Improper updates can “brick” the relay.
Q: Can this relay be used for directional protection? A: Yes. The REF545 is a fully featured numerical relay that supports directional overcurrent, directional earth fault, and distance protection functions, provided the required voltage inputs (VT) are wired.
🔗 Recommended Similar Models
-
REF545EM133AAAC
-
REF615 (Modern replacement series)
-
REF620
-
REX521
-
REF543
-
REM543 (Motor Protection)
-
RET545 (Transformer Protection)
-
REF545EM133AAAD
-
ABB Relion 615 Series
-
ABB Relion 620 Series