Areva MVAJ105RA0802A | Protective Trip Relay

The Areva (formerly GEC Alsthom) MVAJ105RA0802A is a high-speed, heavy-duty tripping relay. Designed for critical protection schemes in electrical substations, it serves as the primary interface between protective relays and circuit breakers. Known for its high immunity to electrical interference and rapid operate time, it ensures that fault clearing commands are executed reliably. For technical datasheets and procurement, please visit Areva/Schneider Electric Protection Solutions.

Areva MVAJ / MVAJ105RA0802A Protective Trip Relay

📊 Technical Specifications

  • Series: MVAJ Tripping Relay

  • Model: MVAJ105RA0802A

  • Function: High-speed, heavy-duty tripping (86 or 94 function)

  • Design: Electromechanical with high-speed reset

  • Weight: Approx. 1.2 kg

  • Original Manufacturer: Areva (now Schneider Electric/Alstom)

  • Mounting: Modular draw-out case (standard M-Series footprint)

🏗️ Application Areas

  • Circuit breaker trip circuit control

  • Protection interlocking schemes

  • High-voltage transformer differential protection

  • Emergency shutdown (ESD) relaying

⚙️ Product Operation & Installation

Manual/Automatic Mode Switching This relay is an automatic electromechanical component. It does not have configurable software modes. It reacts instantaneously to the energization of its trip coil. Following an operation, the mechanical target flag must be manually reset using the front-panel button to prepare the relay for the next fault.

Emergency Stop Operation The MVAJ is a critical link in an emergency stop sequence. When a master relay sends a trip signal, the MVAJ closes its heavy-duty contacts to complete the circuit to the breaker’s shunt-trip coil. It is specifically designed to handle the high inductive loads associated with circuit breaker trip coils without contact welding.

Mechanical Installation Requirements

  • Fixing Method: Flush-mount into the switchgear panel via the draw-out cradle.

  • Space Distance: Maintain at least 75 mm of clearance around the housing to allow for the draw-out mechanism to function and to ensure proper thermal dissipation.

  • Thermal Dissipation: Ensure the substation control room temperature remains within the -10°C to +55°C range to preserve the elasticity of the internal springs and the integrity of the coil insulation.

Electrical Wiring

  • Terminal Definitions: Terminals are located on the rear of the draw-out cradle. Always consult the specific wiring diagram on the relay case, as the “105” series indicates specific coil voltage and contact configurations.

  • Wire Gauge: Use 2.5 mm² stranded copper wire for all tripping circuits. Ensure terminals are properly ferruled to prevent loose connections.

  • Grounding: The metallic chassis is internally connected to the cradle earth pin. Ensure this is bonded to the main substation earth busbar with a minimum 4 mm² copper conductor.

💡 Frequently Asked Questions (Q&A)

Q: What is the “105” designation in the model number? A: In the MVAJ series, the “105” suffix typically identifies the specific contact arrangement, auxiliary supply voltage rating, and operating time characteristics. Always check the nameplate to confirm compatibility with your system.

Q: Can I test this relay without tripping the breaker? A: Yes, you can use a test plug (such as the MMLB type) to isolate the trip outputs, allowing you to safely inject current into the coil to verify the pickup voltage and contact operation.

Q: Why is there a target flag? A: The flag is a mechanical indicator that locks into place when the relay operates. It provides a non-volatile, visual record of which relay initiated a trip—essential for post-fault analysis in substations without sophisticated event recorders.