Product Description
The GE Fanuc IC693MDL940J is a 16-point relay output module designed for the Series 90-30 Programmable Logic Controller (PLC) family. It provides normally open relay contacts for switching external AC or DC loads in industrial automation and machine control applications.
The module contains 16 relay output circuits arranged in four groups of four points. Each output supports a maximum pilot-duty current of 2 A, while each common group supports a maximum current of 4 A.
The IC693MDL940J is suitable for controlling contactors, solenoid valves, indicator lamps, motor starters, and other compatible field devices. Its electromechanical relay outputs provide flexible AC/DC load switching for existing Series 90-30 control systems.

Product Parameters
- Brand: GE Fanuc
- Model: IC693MDL940J
- Product Series: Series 90-30
- Product Name: 16-Point Relay Output Module
- Module Type: Discrete Output Module
- Output Points: 16
- Output Contact Type: Normally Open (Form A)
- Output Configuration: Four groups of four outputs
- Rated Voltage: 24 VDC, 120/240 VAC nominal
- Operating Voltage: 5–30 VDC; 5–250 VAC, 50/60 Hz
- Maximum Output Current: 2 A per point (pilot duty)
- Maximum Current per Common: 4 A
- Minimum Load Current: 10 mA
- Maximum Inrush Current: 5 A
- Maximum Module Load: 16 A, subject to group and channel limits
- ON Response Time: 15 ms maximum
- OFF Response Time: 15 ms maximum
- Isolation: 1500 VAC field-to-logic; 500 VAC between groups
- Backplane Power Consumption: 7 mA from 5 VDC bus and 135 mA from 24 VDC relay bus with all outputs on
- Field Power: Supplied externally by the user
- Output Protection: No onboard output fuses
- Installation: Series 90-30 PLC baseplate, one I/O slot
- Dimensions: Confirm from the hardware revision and installation documentation
- Weight: Approx. 0.40 kg; confirm actual unit
- Country of Origin: Confirm from product label
- Product Status: Legacy / discontinued product family; verify current support
- Product Condition: Confirm the condition of the supplied unit
Main Features
- 16 normally open relay output points.
- Four groups of four outputs with separate common terminals.
- Supports compatible AC and DC field loads.
- Maximum 2 A pilot-duty switching capacity per output.
- Suitable for contactors, solenoids, indicator lamps, and control relays.
- Front-panel LED indicators show output point status.
- Electrical isolation between field circuits and PLC logic.
- Installs in a compatible Series 90-30 PLC baseplate.
Typical Applications
- Industrial machine control
- Motor starter and contactor switching
- Solenoid valve control
- Industrial alarm and indicator circuits
- Packaging and material handling equipment
- Production line automation
- Process equipment control
- Legacy GE Fanuc Series 90-30 PLC maintenance
Installation and Commissioning
- Verify the complete model number IC693MDL940J and inspect the module revision label.
- Confirm compatibility with the installed Series 90-30 PLC baseplate and CPU configuration.
- Review the electrical drawings and identify the four output common groups.
- Isolate the PLC and external field-load power supplies before installation.
- Inspect the module connector, terminal block, and relay output terminals for damage.
- Install the module in the designated I/O slot according to the PLC installation procedure.
- Connect external AC or DC load power to the appropriate common groups.
- Connect field loads to their assigned output points and verify polarity where applicable.
- Check that each common group remains within its 4 A current limit and each output remains within its 2 A pilot-duty rating.
- Restore power and verify the PLC recognizes the module.
- Test each output point individually and confirm the corresponding LED and field device response.
- Check relay switching behavior and confirm that external loads operate correctly before returning the machine to service.
Daily Maintenance and Care
- Inspect terminal blocks and wiring for looseness or overheating.
- Check output LEDs during routine equipment inspections.
- Monitor relay contacts for abnormal switching behavior.
- Check field-load current against the module’s channel and common ratings.
- Inspect the module for dust, moisture, corrosion, and physical damage.
- Verify external load power and protective devices.
- Record relay output faults and replacement history.
- Schedule periodic functional testing for critical output circuits.
Troubleshooting and Common Questions
Q1: What is the main function of the IC693MDL940J?
A: It provides 16 normally open relay outputs for controlling external AC or DC loads in a GE Fanuc Series 90-30 PLC system.
Q2: What is the maximum current per output?
A: The maximum pilot-duty rating is 2 A per output. Each common group is limited to 4 A. Actual allowable current depends on load type and switching conditions.
Q3: Why does an output LED turn on but the field device does not operate?
A: Check the external load power supply, common wiring, terminal connections, field-device condition, and relay contact continuity.
Q4: Why does a relay output remain on after the PLC command is removed?
A: Possible causes include welded relay contacts, incorrect external wiring, or an output command that remains active in the PLC logic. Isolate the circuit and test the relay contacts safely.
Q5: Does the module provide power to external loads?
A: No. The field devices require an external AC or DC power source. The module’s backplane supply powers its internal relay circuitry.
Q6: Does the IC693MDL940J have onboard output fuses?
A: No. External circuit protection must be selected and installed according to the load and wiring design.
Q7: Can the IC693MDL940J replace the IC693MDL930?
A: Not as a direct substitution without checking the application. The IC693MDL930 has a different output configuration and current rating. Confirm wiring, load requirements, and PLC configuration before replacement.
Safety Precautions
- Installation and maintenance must be performed by qualified electrical or automation personnel.
- Isolate both PLC power and external field-load power before handling wiring.
- Do not exceed the 2 A per-point or 4 A per-common limits.
- Provide suitable external overcurrent protection.
- Confirm the AC/DC voltage range and load characteristics before connection.
- Do not assume the module’s internal supply powers field devices.
- Follow the Series 90-30 installation manual and approved plant wiring diagrams.
Recommended GE Fanuc Related Models
The following models belong to the GE Fanuc Series 90-30 PLC family or related I/O range. They have different functions and are not all direct replacements for IC693MDL940J.
- GE Fanuc IC693MDL930 – 8-Point Isolated Relay Output Module
- GE Fanuc IC693MDL931 – 8-Point Relay Output Module, Form C
- GE Fanuc IC693MDL916 – 16-Point Relay Output Module
- GE Fanuc IC693MDL940 – 16-Point Relay Output Module
- GE Fanuc IC693MDL730 – 8-Point 12/24 VDC Positive Logic Output Module
- GE Fanuc IC693MDL731 – 8-Point 12/24 VDC Negative Logic Output Module
- GE Fanuc IC693MDL732 – 8-Point 12/24 VDC Positive Logic Output Module
- GE Fanuc IC693MDL733 – 8-Point 12/24 VDC Negative Logic Output Module
- GE Fanuc IC693MDL740 – 16-Point 12/24 VDC Positive Logic Output Module
- GE Fanuc IC693MDL741 – 16-Point 12/24 VDC Negative Logic Output Module
- GE Fanuc IC693MDL742 – 16-Point 12/24 VDC Output Module with Electronic Short-Circuit Protection
- GE Fanuc IC693MDL754 – 32-Point 12/24 VDC Positive Logic Output Module
- GE Fanuc IC693MDL653 – 32-Point Fast Response Digital Input Module
- GE Fanuc IC693MDL655 – 32-Point 24 VDC Digital Input Module
- GE Fanuc IC693CPU331 – Series 90-30 PLC CPU Module