GE Fanuc | IC698PSA350C | PACSystems RX7i 350W AC Power Supply Module

Product Description

The GE Fanuc IC698PSA350C is a high-capacity power supply module designed for the PACSystems RX7i PLC platform. It converts AC or supported DC input power into regulated DC outputs for the RX7i rack backplane, supplying the power required by the CPU, I/O modules, and other rack-mounted components.

The module provides three DC output rails: +5 VDC, +12 VDC, and -12 VDC, with a combined maximum output capacity of 350 W. It installs directly into Slot 0 of the RX7i main rack and provides power-status monitoring and protective functions.

The IC698PSA350C is intended for industrial control systems with higher backplane power requirements. Forced-air cooling is required to achieve its full rated output capacity.

Product Parameters

  • Brand: GE Fanuc
  • Model: IC698PSA350C
  • Series: PACSystems RX7i
  • Product Name: 350W AC Power Supply Module
  • Product Type: PLC Rack Power Supply
  • Nominal Input Voltage: 120/240 VAC or 125 VDC
  • Input Voltage Range: 85–264 VAC or 100–150 VDC
  • AC Input Frequency: 47–63 Hz
  • Maximum Total Output Power: 350 W
  • +5 VDC Output: 0–60 A
  • +12 VDC Output: 0–12 A
  • -12 VDC Output: 0–4 A
  • Installation Position: Slot 0, RX7i main rack
  • Cooling Requirement: Forced-air cooling for full rated capacity
  • Protection: Overcurrent, overvoltage, short-circuit, and overtemperature protection
  • Place of Manufacture: Not independently verified
  • Product Status: Confirm the condition of the supplied unit
  • Dimensions: Confirm from the physical unit and manufacturer documentation
  • Weight: Approximately 2.0–2.1 kg; confirm for the supplied revision
  • Country of Origin: Confirm from the product label

Main Features

  • 350 W maximum combined DC output for demanding RX7i rack configurations.
  • Three regulated DC output rails for backplane power distribution.
  • Wide-range AC input with additional 100–150 VDC input capability.
  • Power-factor correction during AC operation.
  • Electronic short-circuit and overcurrent protection.
  • Overvoltage and overtemperature protection.
  • Front-panel power switch and status indicators.
  • Rack-mounted slide-in construction for installation in the RX7i main chassis.

Typical Applications

  • GE Fanuc PACSystems RX7i PLC systems
  • Industrial process automation
  • Power generation and utility control
  • Turbine and auxiliary equipment control
  • Manufacturing and production lines
  • Distributed I/O and large PLC rack configurations
  • Industrial machinery and equipment monitoring

Installation and Commissioning

  1. Verify the complete catalog number and hardware revision on the module label before installation.
  2. Confirm that the RX7i rack is designed to accept the IC698PSA350C.
  3. Switch off and isolate the incoming power supply before removing or installing the module.
  4. Inspect the power connector, rack slot, terminals, and module housing for damage or contamination.
  5. Install the module in Slot 0 of the RX7i main rack.
  6. Connect the correct AC or supported DC input according to the manufacturer’s wiring documentation. Verify grounding and input protection.
  7. Confirm that the rack fan tray and airflow arrangement are installed and operating correctly before using the full 350 W capacity.
  8. Apply power and check the front-panel indicators for normal input and output status.
  9. Measure the DC rails where appropriate and verify that the rack load remains within the permitted output limits.
  10. Confirm that the CPU and installed modules start normally without power-related alarms.

Daily Maintenance and Care

  • Check the power supply status indicators during routine equipment inspections.
  • Keep the rack ventilation openings and fan filters free from dust and obstruction.
  • Monitor fan operation and investigate abnormal noise or reduced airflow.
  • Inspect input wiring, grounding, and terminal connections for signs of overheating or loosening.
  • Record abnormal voltage readings, temperature alarms, and unexpected rack shutdowns.
  • Check the rack’s total power demand after adding or replacing modules.
  • Maintain a suitable spare module to reduce downtime in critical control systems.

Troubleshooting and Common Questions

Q1: What is the function of the IC698PSA350C?

It supplies regulated +5 VDC, +12 VDC, and -12 VDC power to the GE Fanuc PACSystems RX7i rack backplane.

Q2: What is its maximum output capacity?

The combined maximum output is 350 W across the three DC output rails. Individual output current limits must also be observed.

Q3: Can it operate from 120 VAC and 240 VAC?

Yes. Its specified AC input range is 85–264 VAC at 47–63 Hz, covering common 120 VAC and 240 VAC supplies.

Q4: Can it operate without a rack fan tray?

The module requires forced-air cooling to deliver its full rated capacity. Operation with convection cooling only requires output derating according to the manufacturer’s thermal specifications.

Q5: Why does the RX7i rack fail to start?

Possible causes include incorrect input wiring, an out-of-range supply voltage, a faulty power supply, poor rack connections, excessive load, or inadequate cooling. Check the input supply, indicators, rack connections, and fan operation before replacing the module.

Q6: Is IC698PSA350C interchangeable with IC698PSA100?

They belong to the same RX7i power supply family, but they have different output capacities. Confirm rack requirements, hardware revision, and system power calculations before substitution.

Q7: What should be checked before purchasing a replacement?

Verify the complete part number, revision suffix, input voltage requirements, connector condition, physical condition, and compatibility with the existing RX7i rack.

Safety Precautions

  • Disconnect and isolate all input power before installation or removal.
  • Hazardous voltage may remain inside the module while input power is connected.
  • Follow the manufacturer’s grounding and wiring requirements.
  • Do not exceed the specified output current or total power capacity.
  • Ensure adequate forced-air cooling for full-capacity operation.
  • Do not install or remove the module in a live system unless the applicable system documentation explicitly permits the procedure.
  • Follow site electrical safety procedures and applicable industrial standards.

Recommended GE Fanuc Models

The following are related RX7i power supply, rack, CPU, and system module references. They are not all direct replacements for IC698PSA350C.

  1. IC698PSA100 – RX7i 100W power supply module
  2. IC698PSA350 – RX7i 350W power supply module
  3. IC698PSD300 – RX7i 300W DC power supply module
  4. IC698CHS009 – RX7i rack assembly
  5. IC698CHS016 – RX7i rack assembly
  6. IC698CHS017 – RX7i rack assembly
  7. IC698CPE010 – RX7i CPU module
  8. IC698CPE020 – RX7i CPU module
  9. IC698CPE030 – RX7i CPU module
  10. IC698CPE040 – RX7i CPU module
  11. IC698CRE020 – RX7i redundant CPU module
  12. IC698ETM001 – RX7i Ethernet interface module
  13. IC698ACC701 – CPU backup battery
  14. IC698PSA350A – RX7i 350W power supply revision
  15. IC698PSA350B – RX7i 350W power supply revision
Share this story: