Net Safety SC310-100 Catalytic Bead Combustible Gas Sensor

📌 Net Safety SC310-100 Catalytic Bead Combustible Gas Sensor Datasheet

1. Product Overview

The Net Safety SC310-100 is a high-performance catalytic bead combustible gas sensor designed for continuous monitoring of flammable gases in industrial environments. Part of the Millennium II series, it offers reliable and accurate detection of combustible gases at parts-per-million (ppm) levels, ensuring early warning and safety in hazardous areas.

2. Technical Specifications

🔧 Parameter 📄 Specification
Model Number SC310-100
Type Catalytic Bead Combustible Gas Sensor
Detection Range 0–100% Lower Explosive Limit (LEL)
Response Time ≤ 10 seconds to 90% of final value
Sensitivity ±2% of full scale
Operating Temperature -40°C to +70°C
Humidity Range 0% to 95% non-condensing
Power Supply 24 VDC
Output Signal 4–20 mA (analog)
Enclosure Material Aluminum or Stainless Steel
Dimensions 150 mm x 100 mm x 35 mm
Weight 0.45 kg
Certifications CE, ATEX, UL, CSA
Warranty 5 years

3. Key Features

  • Non-selective Response: Detects both hydrocarbon and non-hydrocarbon based combustible gases.
  • SensorGuard Technology: Protects against exposure to high gas concentrations, extending sensor life.
  • Low Power Consumption: Designed for energy efficiency in continuous monitoring applications.
  • Long Sensor Separation: Supports sensor separation distances up to 2,000 feet, reducing wiring complexity.
  • Rugged Design: Built to withstand harsh industrial environments, ensuring reliable performance.

4. Installation and Maintenance

Installation Guidelines

  • Mounting: Secure the sensor to a suitable surface using the provided mounting hardware. Ensure proper alignment for optimal gas detection.
  • Wiring: Connect the sensor to the control system using appropriate cables. Follow the wiring diagram provided in the installation manual to ensure correct connections.
  • Calibration: Perform calibration using a certified calibration gas mixture. Follow the calibration procedure outlined in the user manual to ensure accurate readings.

Maintenance Tips

  • Regular Inspection: Check the sensor for any signs of physical damage or contamination. Clean the sensor housing periodically to maintain optimal performance.
  • Calibration Frequency: Calibrate the sensor at regular intervals as recommended by the manufacturer, typically every 90 days, to ensure accurate gas detection.
  • Sensor Replacement: Replace the sensor if it shows signs of degradation or if calibration fails to bring readings within acceptable limits.

Usage Precautions

  • Avoid Exposure to Contaminants: Do not expose the sensor to substances that may poison the catalytic bead, such as silicones, lead, or sulfur compounds.
  • Proper Ventilation: Ensure the installation area has adequate ventilation to allow for the dispersion of gases and prevent accumulation.
  • Electrical Safety: Follow all electrical safety guidelines during installation and maintenance to prevent electrical hazards.

5. Similar Products

📌 Model 🔗 Link Description
SC310-200 Link High-sensitivity sensor for low-concentration detection.
SC310-300 Link Extended range sensor for large area coverage.
SC310-400 Link Sensor with built-in display for local monitoring.
SC310-500 Link Wireless communication-enabled sensor for remote monitoring.
SC310-600 Link Explosion-proof sensor for hazardous environments.

6. Purchase Information

For more details or to purchase the SC310-100 Catalytic Bead Combustible Gas Sensor, please visit the following links:

This sensor provides a reliable solution for combustible gas detection, ensuring safety and compliance in industrial applications.

Share this story: