📌 Net Safety SC310-100 Catalytic Bead Combustible Gas Sensor Datasheet
1. Product Overview
The Net Safety SC310-100 is a high-performance catalytic bead combustible gas sensor designed for continuous monitoring of flammable gases in industrial environments. Part of the Millennium II series, it offers reliable and accurate detection of combustible gases at parts-per-million (ppm) levels, ensuring early warning and safety in hazardous areas.
2. Technical Specifications
🔧 Parameter | 📄 Specification |
---|---|
Model Number | SC310-100 |
Type | Catalytic Bead Combustible Gas Sensor |
Detection Range | 0–100% Lower Explosive Limit (LEL) |
Response Time | ≤ 10 seconds to 90% of final value |
Sensitivity | ±2% of full scale |
Operating Temperature | -40°C to +70°C |
Humidity Range | 0% to 95% non-condensing |
Power Supply | 24 VDC |
Output Signal | 4–20 mA (analog) |
Enclosure Material | Aluminum or Stainless Steel |
Dimensions | 150 mm x 100 mm x 35 mm |
Weight | 0.45 kg |
Certifications | CE, ATEX, UL, CSA |
Warranty | 5 years |
3. Key Features
- Non-selective Response: Detects both hydrocarbon and non-hydrocarbon based combustible gases.
- SensorGuard Technology: Protects against exposure to high gas concentrations, extending sensor life.
- Low Power Consumption: Designed for energy efficiency in continuous monitoring applications.
- Long Sensor Separation: Supports sensor separation distances up to 2,000 feet, reducing wiring complexity.
- Rugged Design: Built to withstand harsh industrial environments, ensuring reliable performance.
4. Installation and Maintenance
Installation Guidelines
- Mounting: Secure the sensor to a suitable surface using the provided mounting hardware. Ensure proper alignment for optimal gas detection.
- Wiring: Connect the sensor to the control system using appropriate cables. Follow the wiring diagram provided in the installation manual to ensure correct connections.
- Calibration: Perform calibration using a certified calibration gas mixture. Follow the calibration procedure outlined in the user manual to ensure accurate readings.
Maintenance Tips
- Regular Inspection: Check the sensor for any signs of physical damage or contamination. Clean the sensor housing periodically to maintain optimal performance.
- Calibration Frequency: Calibrate the sensor at regular intervals as recommended by the manufacturer, typically every 90 days, to ensure accurate gas detection.
- Sensor Replacement: Replace the sensor if it shows signs of degradation or if calibration fails to bring readings within acceptable limits.
Usage Precautions
- Avoid Exposure to Contaminants: Do not expose the sensor to substances that may poison the catalytic bead, such as silicones, lead, or sulfur compounds.
- Proper Ventilation: Ensure the installation area has adequate ventilation to allow for the dispersion of gases and prevent accumulation.
- Electrical Safety: Follow all electrical safety guidelines during installation and maintenance to prevent electrical hazards.
5. Similar Products
📌 Model | 🔗 Link | Description |
---|---|---|
SC310-200 | Link | High-sensitivity sensor for low-concentration detection. |
SC310-300 | Link | Extended range sensor for large area coverage. |
SC310-400 | Link | Sensor with built-in display for local monitoring. |
SC310-500 | Link | Wireless communication-enabled sensor for remote monitoring. |
SC310-600 | Link | Explosion-proof sensor for hazardous environments. |
6. Purchase Information
For more details or to purchase the SC310-100 Catalytic Bead Combustible Gas Sensor, please visit the following links:
This sensor provides a reliable solution for combustible gas detection, ensuring safety and compliance in industrial applications.