Product Description
The ABB AI03 is an 8-channel RTD analog input module designed for the ABB Symphony Plus SD Series I/O system. It acquires temperature signals from resistance temperature detectors and converts them into digital process data for monitoring, control, and automation applications.
Each channel can be independently configured for supported RTD sensor types and 2-wire, 3-wire, or 4-wire wiring arrangements. The module uses 16-bit analog-to-digital conversion and provides group isolation between field signals and control logic. Automatic calibration reduces the need for manual calibration procedures.
Main Functions and Applications
• Acquires temperature signals from up to 8 RTD sensors.
• Supports 100 Ω Platinum RTDs, including U.S. and European standards.
• Supports 120 Ω Nickel and Chinese 53 Ω Copper RTD sensors.
• Provides independently configurable input channels.
• Converts RTD resistance measurements into digital process values.
• Supports temperature monitoring in power generation, chemical processing, industrial utilities, and manufacturing systems.
• Provides front-panel status and channel diagnostic indicators.
Product Parameters
Brand: ABB
Model: AI03
Product Type: RTD Analog Input Module
Product Series: Symphony Plus SD Series I/O
Number of Channels: 8
Input Signal Type: Resistance Temperature Detector (RTD)
Supported Sensors: 100 Ω Platinum, 120 Ω Nickel, Chinese 53 Ω Copper
Wiring Configuration: 2-wire, 3-wire, and 4-wire
A/D Resolution: 16-bit with polarity
A/D Update Rate: 450 ms for all 8 channels
Measurement Accuracy: ±0.1% of full-scale range (FSR = 500 Ω)
Module Power Supply: 24 VDC ±10%
Typical Current Consumption: 68 mA
Maximum Current Consumption: 76 mA
Field-to-Logic Isolation: 1500 V, up to 1 minute
Channel Isolation: 1 group of 8 channels, 1500 V, up to 1 minute
Maximum Field Cable Length: 600 m
Operating Temperature: -40 to +70 °C
Storage Temperature: -40 to +85 °C
Mounting: Horizontal row or vertical column
Protection Rating: IP20
Dimensions: Approximately 190 × 27 × 106 mm
Weight: Approximately 226 g
Country of Origin: Verify from product nameplate
Product Status: Active in ABB’s published product selector
Power Requirements: External 24 VDC supply
Discontinued Status: Not listed as discontinued in ABB’s current product selector
Installation and Commissioning
- Confirm that the AI03 module is installed in a compatible ABB Symphony Plus SD Series I/O configuration.
- Verify the mounting base. ABB lists HBS01-CJC and VBS01-CJC as compatible mounting units for AI03.
- Check the 24 VDC supply and confirm correct power connections before energizing the system.
- Connect each RTD sensor using the appropriate 2-wire, 3-wire, or 4-wire arrangement.
- Confirm that the configured sensor type matches the actual field instrument.
- Configure the I/O device parameters using Function Code FC 221.
- Configure individual input channel settings using FC 222, including engineering units and high/low alarm limits.
- After startup, check the Run, Fault, and individual channel status LEDs.
- Compare displayed temperature values with a calibrated reference instrument before returning the process to normal operation.
Daily Maintenance and Care
• Check the module’s Run and Fault indicators during routine inspections.
• Monitor temperature readings for unexpected fluctuations or abnormal deviations.
• Inspect RTD wiring, terminal connections, and cable shielding.
• Check for loose connections, corrosion, moisture, or signs of overheating.
• Keep the module and mounting area clean and within the specified operating environment.
• Record recurring channel faults and temperature measurement deviations.
• Confirm sensor configuration after replacing an RTD or changing field wiring.
Troubleshooting and Common Problems
No temperature reading:
Check the 24 VDC supply, field wiring, mounting base connections, and channel configuration.
Incorrect temperature values:
Verify the RTD sensor type, resistance specification, wiring arrangement, and engineering unit settings.
RTD open-circuit alarm:
Inspect the sensor and field cable for broken conductors or loose terminals. ABB specifies an open-circuit detection time of less than 5 seconds.
Unstable temperature readings:
Check cable routing, grounding, terminal tightness, and possible electrical interference from nearby power equipment.
Module Fault LED active:
Review the system diagnostics, inspect the module power supply, and check the I/O configuration and mounting connections.
Channel-specific faults:
Check the affected RTD sensor and wiring independently before replacing the module.
Safety Precautions
• Isolate the relevant power sources before installation or wiring work.
• Follow ABB’s system-specific installation and maintenance instructions.
• Do not connect voltage or current signals to RTD input terminals.
• Verify the sensor type and terminal arrangement before applying power.
• Observe electrostatic discharge precautions when handling the module.
• Confirm that the control system is in a safe state before removing or replacing I/O hardware.
Recommended ABB Models
The following models are related ABB Symphony Plus SD Series I/O products. They are reference options for system expansion or spare-parts planning, not confirmed direct replacements for AI03.
- AI04 – RTD analog input module in the SD Series.
- AI01 – Analog input module for process signal acquisition.
- AI02 – Analog input module with HART-related functionality.
- AI05 – Analog input module for industrial process measurements.
- AI06 – Universal analog input module.
- AD11 – Mixed analog and digital I/O module.
- AO01 – Analog output module.
- AO02 – Analog output module for process control.
- AO05 – Analog output module in the SD Series.
- DI01 – Digital input module.
- DI02 – Digital input module for field status signals.
- DI03 – Digital input module.
- DI04 – Digital input module.
- DO01 – Digital output module.
- DO02 – Digital output module for industrial control applications.














_副本.jpg)