Product code: N/A
EMERSON | 2500M/AI4UNIV | Four-Channel Universal Analog Input Module
¥99,999.00 Original price was: ¥99,999.00.¥1,588.00Current price is: ¥1,588.00.
This image and price are not for reference. If you need to inquire, please contact me!
🌍Country of origin: USA France Germany Estonia Norway UK
⌚Delivery date: in stock
🛠After-sales service: brand new with one year warranty
⚙️ Product Category: Module/Controller/Server/Motor/Touch Screen
🕰Warranty: 12 months/365 days
☎️ Please contact me: 15359029662 Ms. Amy Sun
📎Chinese official website: www.dcsplcabb.com
📩Email: geabbamy@gmail.com
💬Whatsapp: +86 15359029662
If you have any products that you cannot find, you can consult anytime.
Detailed content
Product Overview
The Emerson Eurotherm 2500M/AI4UNIV is a four-channel universal analog input module designed for the 2500 distributed I/O and control system. It accepts thermocouple, millivolt (mV), and milliampere (mA) signals for industrial process measurement and control.
The module converts field sensor signals into measurement data for use by the compatible control system. When configured with the appropriate terminal unit, it supports thermocouple cold-junction compensation (CJC), voltage measurement, and current-loop measurement.
The 2500M/AI4UNIV is suitable for temperature monitoring, process instrumentation, and industrial automation applications that require multiple analog measurement channels in a compact modular system.
Key Features
- Four universal analog input channels
- Supports thermocouple, mV, and mA input types
- Thermocouple linearization for multiple sensor types
- Configurable input filtering
- High common-mode and series-mode noise rejection
- System isolation for industrial control applications
- Compatible terminal units available for different sensor connections
- Designed for the Emerson Eurotherm 2500 I/O platform
Product Datasheet
| Parameter | Description |
|---|---|
| Brand | Emerson / Eurotherm |
| Model | 2500M/AI4UNIV |
| Series | Eurotherm 2500 I/O |
| Product Name | Four-Channel Universal Analog Input Module |
| Place of Manufacture | To be confirmed |
| Product Status | Availability and condition to be confirmed |
| Dimensions | Exact module dimensions to be confirmed |
| Weight | To be confirmed |
| Country of Origin | To be confirmed |
| Input Channels | 4 |
| Input Types | Thermocouple, mV, mA |
| Voltage Input Range | −150 mV to +150 mV |
| Current Input Range | Approximately −22 mA to +22 mA, with the specified terminal-unit shunt arrangement |
| Thermocouple Types | J, K, L, R, B, N, T, S, C, PL2, and configurable types |
| Maximum Power Consumption | 2 W |
| Maximum Current Consumption | 100 mA, as specified in the technical documentation |
| System Isolation | Reinforced isolation, up to 264 V AC maximum in the published specification |
| Cold-Junction Compensation | Supported with the appropriate thermocouple terminal unit |
| Discontinued Status | To be confirmed |
Typical Applications
- Industrial temperature measurement
- Process control and monitoring
- Thermocouple-based temperature acquisition
- Analog current-loop measurement
- Voltage signal acquisition
- Distributed I/O systems
- Manufacturing and process automation
Troubleshooting Guide
Q1: The module does not detect an analog input.
Verify that the field wiring is connected to the correct terminals and that the input type is configured correctly. Check the sensor, terminal unit, and module seating.
Q2: Temperature readings are inaccurate.
Confirm the thermocouple type, polarity, wiring condition, and cold-junction compensation configuration. Check whether the correct terminal unit is installed.
Q3: The current input reading is incorrect.
Verify the current-loop wiring and the terminal unit’s shunt configuration. Confirm that the signal source is within the supported input range.
Q4: The measured value fluctuates.
Inspect cable shielding, grounding, sensor connections, and electrical interference. Apply suitable input filtering if permitted by the control application.
Q5: The controller does not recognize the module.
Check the 2500 I/O system configuration, module seating, terminal-unit compatibility, and controller diagnostics.
Installation and Safety Precautions
- Isolate relevant electrical circuits before connecting or removing the module.
- Verify the terminal-unit type before connecting thermocouples, mV signals, or current loops.
- Follow the manufacturer’s grounding and shielding recommendations.
- Do not exceed the specified input ranges or isolation limits.
- Confirm the module configuration and input scaling before commissioning.
- Perform calibration and functional checks before returning the control system to service.
Frequently Asked Questions
Q1: What is the Emerson 2500M/AI4UNIV used for?
It acquires four channels of analog process measurements, including thermocouple, millivolt, and milliampere signals.
Q2: Does it support thermocouple inputs?
Yes. It supports multiple thermocouple types, with cold-junction compensation provided through the appropriate terminal-unit configuration.
Q3: Does the module support 4–20 mA signals?
It supports milliampere input measurement. Confirm the selected terminal unit and configured range for the intended current-loop application.
Q4: Which terminal unit is compatible?
The published order-code information identifies terminal-unit options including 2500T/AI4/TC/NONE for thermocouple inputs with CJC, 2550T/AI4/mV/NONE for mV inputs, and 2550T/AI4/mA/NONE for mA inputs. Verify the exact hardware and revision before ordering.
Q5: Can it be used as a standalone controller?
No. It is an I/O module intended for use within a compatible Eurotherm 2500 system.
Q6: Is this module discontinued?
Its current production status has not been confirmed. Check with Emerson or a specialist industrial automation supplier.
Recommended Related Emerson / Eurotherm Models
The following modules and system components are related to the Eurotherm 2500 platform. They have different functions and are not direct substitutes for the 2500M/AI4UNIV.
- 2500M/AO2UNIV — Two-channel analog output module
- 2500M/DI8LOGIC — Eight-channel logic-input module
- 2500M/DI6HVAC/230V — Six-channel AC voltage input module
- 2500T/AI4/TC/NONE — Four-channel thermocouple terminal unit with CJC
- 2550T/AI4/mV/NONE — Terminal unit for mV inputs
- 2550T/AI4/mA/NONE — Terminal unit for mA inputs
- 2500T/AO2/UNIV/NONE — Terminal unit for the analog output module
- 2550T/AO2/DCONNECT — Analog output terminal unit with disconnects
- 2500E/S/4LOOPUW/PROFIBUS — 2500 controller configuration with four control loops and PROFIBUS
- 2500E/S/8LOOP/PROFIBUS — 2500 controller configuration with eight control loops and PROFIBUS
- 2500E/S/8LOOPUW/MODBUS — 2500 controller configuration with eight loops and Modbus
- 2500E/S/8LOOPUW/ENET MBUS — 2500 controller configuration with Ethernet/Modbus
- Eurotherm 2500 Controller — Modular process control platform
- Eurotherm 2408 — Temperature and process controller
- Eurotherm 3504 — Advanced process and temperature controller
Ordering Recommendation: Confirm the exact module code, condition, and terminal-unit requirements before purchase. The 2500M/AI4UNIV must be matched to the intended input type and the compatible Eurotherm 2500 system configuration.













_副本.jpg)