Product Introduction
The Vibro-Meter 200-560-000-113 is the IOC4T input/output card for the VM600 machinery protection and condition monitoring system. Manufactured under the Vibro-Meter product line, it provides the signal interface for compatible MPC4 machinery protection cards, connecting vibration and speed sensors with the monitoring and protection system.
The IOC4T supports four dynamic measurement channels and two tachometer (speed) channels. It also provides relay contacts, analog outputs, and buffered sensor-signal outputs for compatible external monitoring equipment. It is used in rotating machinery applications such as turbines, compressors, pumps, and other critical industrial equipment.
This is an earlier IOC4T hardware version. Manufacturer documentation identifies the 200-560-000-113 version as a pre-RoHS design with a buffered dynamic signal output impedance of 2,000 ohms. Verify compatibility with the installed MPC4 card and rack before replacement.
Key Features
- Manufacturer: Vibro-Meter
- Model: 200-560-000-113
- Product Series: VM600
- Card Designation: IOC4T
- Product Type: Input/output interface card
- Dynamic Measurement Inputs: 4 channels
- Tachometer Inputs: 2 channels
- Additional Interfaces: Relay contacts, analog outputs, buffered sensor outputs, and digital control signals
- Primary Application: Machinery vibration monitoring and protection
- Installation: Compatible VM600 rack
- Hardware Revision: Earlier, pre-RoHS version
Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | Vibro-Meter |
| Model | 200-560-000-113 |
| Series | VM600 Machinery Protection System |
| Product Name | IOC4T Input/Output Card |
| Product Type | Signal interface and I/O card |
| Dynamic Signal Inputs | 4 |
| Tachometer Inputs | 2 |
| Relay Outputs | 4 relay contact outputs |
| Analog Outputs | DC signal outputs; see manufacturer documentation for channel details |
| Digital Signals | DSI control signals, including AR, DB, and TM |
| Buffered Outputs | Raw dynamic sensor outputs |
| Connectors | Three 16-contact screw-terminal connectors: J1, J2, and J3 |
| Height | 262 mm (6U) |
| Width | 20 mm |
| Depth | 125 mm |
| Weight | Approximately 0.25 kg |
| Place of Manufacture | To be confirmed |
| Country of Origin | To be confirmed from the product label |
| Power Requirements | Installed in a compatible VM600 rack; confirm system requirements |
| Hardware Status | Earlier, pre-RoHS version |
| Discontinued | Confirm current availability with the supplier |
Typical Applications
- Steam and gas turbine protection
- Compressor and pump vibration monitoring
- Rotating machinery condition monitoring
- Shaft vibration and speed measurement
- Integration of machinery monitoring signals with external control and alarm systems
- Maintenance of installed VM600 machinery protection systems
Installation and Troubleshooting
Before installation
- Confirm the complete ordering number and hardware revision.
- Verify compatibility with the installed MPC4 protection card.
- Check the rack slot, terminal connectors, and field wiring against the system drawings.
- Confirm whether the replacement version has the same signal-output characteristics as the original.
If sensor signals are missing
- Inspect sensor wiring and terminal connections.
- Verify the correct sensor type and channel assignment.
- Check the associated MPC4 card and system diagnostics.
If relay or analog outputs are incorrect
- Check relay wiring and configured output assignments.
- Verify the monitoring system’s channel configuration.
- Confirm that the connected equipment is compatible with the output signal characteristics.
If replacing an earlier version
- Compare the existing card’s ordering number and buffered output impedance with the replacement.
- Check the manufacturer’s compatibility notes before mixing different IOC4T and MPC4 revisions.
Safety Precautions
- Follow the machinery protection system’s approved maintenance and isolation procedures.
- Do not remove or replace cards without confirming whether the system permits the operation while energized.
- Use electrostatic-discharge protection when handling the circuit board.
- Confirm wiring and output ratings before connecting external equipment.
- Carry out functional checks after installation to verify that monitoring and protection signals operate correctly.
Frequently Asked Questions
Q1: What is the VIBRO-METER 200-560-000-113?
It is the IOC4T input/output card used in compatible VM600 machinery protection systems.
Q2: How many dynamic measurement channels does it support?
It supports four dynamic measurement channels and two tachometer inputs.
Q3: Which card works with the IOC4T?
It is designed to interface with a compatible MPC4 machinery protection card. Confirm the specific MPC4 version and system configuration before installation.
Q4: Is 200-560-000-113 a RoHS-compliant version?
No. The manufacturer’s datasheet identifies this ordering number as an earlier version that is not RoHS compliant. Later variants have different ordering numbers and output characteristics.
Q5: What are its dimensions and weight?
The manufacturer’s datasheet lists a height of 262 mm, a width of 20 mm, a depth of 125 mm, and an approximate weight of 0.25 kg.
Q6: Can it be replaced by 200-560-000-114?
Do not assume direct interchangeability without checking the manufacturer’s compatibility documentation. The 200-560-000-114 is a later RoHS-compliant version with different buffered output impedance characteristics.
Recommended Related Vibro-Meter Models
The following models are related VM600 machinery protection and condition monitoring components. They are not all direct replacements for the IOC4T card.
- 200-510-070-113 – MPC4 machinery protection card variant
- 200-510-078-115 – MPC4 machinery protection card variant
- 200-560-000-114 – Later IOC4T I/O card version
- 200-560-000-211 – IOC4T separate-circuit version
- 200-560-000-212 – Later IOC4T separate-circuit version
- 200-582-500-013 – RPS6U power supply module
- 204-607-041-01 – VM600 monitoring-system component
- 204-677-000-003 – VM600 system component
- 254-772-000-224 – Vibro-Meter monitoring-system component
- TQ402 – Eddy-current proximity probe family
- 111-402-000-013 – TQ402 proximity probe variant
- IQS452 – Signal conditioner family
- 204-452-000-221 – IQS452 signal conditioner variant
- MPC4SIL – Safety-oriented machinery protection card family
- VM600 CPUM – Rack controller and communication module family
Verify every complete ordering number and system revision before purchasing replacement parts.