TRICONEX DI2301 Digital Input Module | TMR Safety System

The TRICONEX DI2301 is an input module designed for the Tricon Triple Modular Redundant (TMR) system. It features 16 isolated input channels, providing fault tolerance and continuous operation for industrial safety instrumented systems (SIS).


Technical Specifications | DI2301 Parameters

Parameter Specification
Manufacturer Schneider Electric (Triconex)
Origin USA
Module Type Digital Input (TMR)
Number of Channels 16, Isolated
Input Voltage 24 VDC
Dimensions 228mm x 190mm x 32mm
Weight 0.82 kg
Power Consumption < 10 Watts
Operating Temperature 0°C to 60°C

Operational Precautions | Best Practices

  • Hot Swapping: Supports module replacement during operation. Ensure the new module version matches the existing system configuration.

  • Wiring Integrity: Use shielded and grounded 24V DC wiring to prevent signal interference.

  • Firmware Sync: Verify that the module firmware is compatible with the TriStation 1131 software settings.

  • Handling: Always use an ESD wrist strap when touching the module to prevent damage to internal components.


Common Q&A | Technical Support

Q: What is the TMR feature for this module? A: Triple Modular Redundant (TMR) means the module uses three independent circuits to vote on signals, preventing a single hardware failure from stopping the system.

Q: Can the DI2301 detect cable faults? A: Yes, it includes diagnostic functions to identify open or short circuits based on the system setup.

Q: Does it require external power? A: Yes, the digital inputs need an external 24V DC power source to operate the loops.


Recommended Similar Models | 2000 Series

  1. DI2351 | 24 VDC Digital Input Module (32-channel)

  2. DO2401 | 24 VDC Digital Output Module

  3. AI3301 | Analog Input Module

  4. DI2401 | 115 VAC/VDC Digital Input Module

  5. DO2401L | Low-power Digital Output Module


Would you like me to provide the product descriptions for any of these five similar models next?